Hospital Elevator

Planning > Dimensions > Hospital / Streture / Bed Lift

Manual and Automatic Door

Space Requirement For Manual Door
LOAD CAR INSIDE ELEVATOR SHAFT ENTRANCE MACHINE ROOM
Persons Kg. A B C D E K L M
15 1020 950 2400 1750 2700 900 3000 4000 2700
20 1360 1300 2400 2150 2700 1200 3500 4000 2700
26 1768 1600 2400 2450 2700 1200 4000 4000 2700
 

Pit Depth= 1600 mm
Over Head Room Height= 4800 mm

All Dimensions in mm.
Elevator Shaft dimensions
are minimum finished dimensions.

Space Requirements (Automatic Doors)
LOAD CAR INSIDE ELEVATOR SHAFT ENTRANCE MACHINE ROOM
Persons Kg. A B C D E K L M
15 1020 950 2400 1800 3000 900 3500 4000 2700
20 1360 1300 2400 2200 3000 1200 4000 4000 2700
26 1768 1600 2400 2400 3000 1200 4200 4000 2700
 

Pit Depth= 1600 mm
Over Head Room Height= 4800 mm
Note: For the requirements of opening sizes greater than 1000 mm for automatic doors, please contact our branch sales office.

All Dimensions in mm.

Elevator Shaft dimensions
are minimum finished dimensions.